HVAC Air Velocity Transmitters

 

Technical Inquiries

support-form3

The hot film anemometer (HFA) is made of a thin, structured, metallic resistive film (“heater”) which is deposited onto a substrate. In the operating state of the HFA the electrical power heats the heater up to a certain temperature. An air-flow of ambient temperature cools the heater down until equilibrium between the electrical Joule heat and the thermal heat loss is reached.Read more

 

Air Velocity Miniature Probe for Medium Velocity
HVAC Series EE671

 

EE671_small

 

Specifications

  • Working ranges: 0 – 1000 ft/min (0 – 5 m/s)
    0 – 2000 ft/min (0 – 10 m/s
    0 – 3000 ft/min (0 – 15 m/s)
    0 – 4000 ft/min (0 – 20 m/s)
  • Output: 0 – 1 V  / 0 – 15 V / 0 – 10 V (max. 1 mA)
  • Supply voltage: 10 – 29 Vdc for 0 – 1 V and 0 – 5 V output
    15 – 29 Vdc for 0 – 10 V outpuy
  • Cable or M12 connector
  • Low angular dependence
  • Low sensitivity to shocks
  • Almost non-directional
  • Good resistance to pollutants

 

Air Velocity Miniature Probe for Low Velocity
HVAC Series EE576

 

EE576_small

 

Specifications

  • Working ranges: 0 – 200 ft/min (0 – 1 m/s)
    0 – 400 ft/min (0 – 2 m/s)
  • Output: 0 – 5 V / 0 – 10 V (max 1 mA)
  • Supply voltage: 10 – 19 Vdc for 0 – 5 V output
    19 – 29 Vdc for 0 – 10 V output
  • Cable lenght 1.5 ft (0.5 m) or 6.6 ft (2 m)
  • Low angular dependence
  • Low sensitivity to shocks
  • Almost non-directional
  • Good resistance to pollutants

 

Air Velocity Transmitter for Medium Velocity
HVAC Series EE65

 

 

Specifications

  • Working ranges: 0 – 2000 / 3000 / 4000 ft/min – selectable
                                   0 – 10 / 15 / 20 m/s – selectable
  • Output: 0 – 10 Vdc / 4 – 20 mA – selectable
  • Duct and remote probe versions
  • Low angular dependence
  • Low sensitivity to shocks
  • Almost non-directional
  • Good resistance to pollutants

 

Air Velocity Transmitter for Low Velocity
Clean Room Series EE660

 

 

Specifications

  • Working ranges: 0 – 200 / 300 / 400 ft/min – selectable
                                     0 – 1.0 / 1.5 / 2.0 m/s – selectable
  • Output: 0 – 10 Vdc / 4 – 20 mA – selectable
  • Measurement down to “0” ft/min (m/s)
  • Wall, duct and remote probe versions
  • Low angular dependence
  • Low sensitivity to shocks
  • Almost non-directional
  • Good resistance to pollutants
  • Display optional

 

pdf  Air Velocity Sensors
pdf  Measuring Air Velocity
pdf  Humidity Influence on Air Velocity Measurement
pdf  IP / NEMA – A Comparison

 

 

 